PFXGP4G01DNWLS

Standard product information
Family
Hardware
Series
Data Collection Devices
Model
PFXGP4G01DNWLS
End of sales
2024/09/30
End of repair
2027/09/30
Repair Service Remark
-
Replacement option 1
Replacement code 1
PFXSTM6B00DE
Replacement code 1 comment
STM6000 Series (GP-Pro EX)
DC power supply
Display resolution different
DIN Rail mount
Blink function is not supported
For more details, refer to the "Replacement book".
Specification
Specifications

Electrical Specifications

Model# PFXGP4G01DNWLS
Rated input voltage 24Vdc
Input voltage limits 19.2 to 28.8Vdc
Voltage drop 5ms or less
Power consumption Maximum power consumption 11W or less
When power is not supplied to external devices 7W or less
In-rush current 30A or less
Voltage endurance 1,000 Vac, 20 mA for 1 minute (between charging and FG terminals)
Insulation resistance 500 Vdc, 10 MΩ or more (between charging and FG terminals)
 

Environmental Specifications

Model# PFXGP4G01DNWLS
Surrounding air temperature 0 to 60°C (32 to 140 °F)
Storage temperature -20 to 60°C (-4 to 140 °F)
Surrounding air and storage humidity 10% to 90% RH (Non condensing, wet bulb temperature 39 °C [102.2 °F] or less)
Dust 0.1mg/m3 (10-7 oz/ft3) or less (non-conductive levels)
Pollution degree Pollution degree 2
Corrosive gases Free of corrosive gases
Atmospheric pressure (operating altitude) 800 to 1,114 hPa (2,000 m [6,561 ft] or lower)
Vibration resistance IEC/EN 61131-2 compliant
5 to 9 Hz Single amplitude 3.5 mm (0.14 in)
9 to 150 Hz Fixed acceleration: 9.8 m/s2
X, Y, Z directions for 10 cycles (approximately 100 minutes)
Shock resistance IEC/EN 61131-2 compliant
147 m/s2, X, Y, Z directions for 3 times
Noise immunity Noise voltage: 1,000 Vp-p
Pulse duration: 1 μs
Rise time: 1 ns
(via noise simulator)
Electrostatic discharge immunity Contact discharge method: 6k V
Air discharge method: 8 kV
(IEC/EN 61000-4-2 Level 3)
 

Memory

Model# PFXGP4G01DNWLS
Application Memory Editor - GP-Pro EX: 
Media: FLASH EPROM
Screen Area *1: 32MB
User Font Area: 8MB
Logic Program Area: 132KB (Equivalent to 15,000 steps)
Free Space: None

Removable System: No
Backup Memory Editor - GP-Pro EX: 
Screen Area: SRAM 320KB
Variable Area: SRAM 64KB

Battery: Replaceable battery / Primary battery for clock data backup

*1 Use the screen area when the user font area's capacity is exceeded - for example, when an image font or a picture font is used.

 

Interface Specifiations

Model# PFXGP4G01DNWLS
Serial interface (PLC/COM1) Asynchronous transmission: RS-232C/422/485
Data length: 7 or 8 bits
Stop bit: 1 or 2 bits
Parity: None, odd, or even
Data Transmission Speed: 2,400 to 115,200 bps
Maximum transmission distance: With RS-232: 15 m (49.2 ft), With RS-422 at 115,200 bps: 1,200 m (3,937 ft)
Serial interface (HMI) Asynchronous transmission: RS-232C/422/485
Data length: 7 or 8 bits
Stop bit: 1 or 2 bits
Parity: None, odd, or even
Data Transmission Speed: 2,400 to 115,200 bps
Maximum transmission distance: With RS-232: 15 m (49.2 ft), With RS-422 at 115,200 bps: 1,200 m (3,937 ft)
USB (Type A) interface Connector: USB2.0 (Type A) x 1
Power supply voltage: 5 Vdc ±5 %
Maximum current supplied: 500 mA/port
Maximum transmission distance: Less than 5 m (16.4 ft)
USB (mini B) interface Connector: USB2.0 (mini B) x 1
Maximum transmission distance: Less than 5 m (16.4 ft)
Ethernet interface Connector: Modular jack (RJ-45) x 1
Standard: IEEE802.3u, 10BASE-T/100BASE-TX
Maximum transmission distance: 100 m (328.1 ft)
SD Card SD Card Slot x 1
SD/SDHC card of up to 32 GB
 

Structural Specifications

Model# PFXGP4G01DNWLS
Grounding Functional grounding: Grounding resistance of 100 Ω, 2 mm2 (AWG 14) or thicker wire, or your country's applicable standard (same for FG and SG terminals).
Cooling method Natural air circulation
Structure Rating *2: Equivalent to IP20
Installation configuration: 35 mm (1.38 in) DIN rail or panel mounted (IEC 60715 compliant)
External dimensions W46 x H162 x D126 mm (W1.81 x H6.38 x D4.96 in.)
Weight 700 g (1.54 lb) or less