Model (Global Code): HTB1C0DM9LP (PFXHTB1C0DM9LP)
Common Specifications
No. of EX Modules that can be connected | Up to 7 units per HTB |
---|---|
Input Voltage | DC24V |
Rated Voltage | DC20.4 to 26.4V (including ripple) |
Power Consumption | 19W (Communication module with (max.) 7 EX modules.) |
Installation Configuration | Attachment via 35mm DIN rail |
Weight | 185g [0.4lb] max. (unit only) |
Input Specifications
Input Points | 12 points with common line |
---|---|
Input Type | Source/ Sink input |
Rated Input Current | 5mA/ input (DC24V) (I0, I1, I6, I7) 7mA/ input (DC24V) (I2 to I5, I8 to I11) |
Input Impedance | 5.0kΩ (I0, I1, I6, I7) 3.4kΩ (I2 to I5, I8 to I11) |
Input Delay Time | 35μs + filter value (I0, I1, I6, I7) 40μs + filter value (I2 to I5, I8 to I11) 45μs + filter value (I0, I1, I6, I7) 150μs + filter value (I2 to I5, I8 to I11) |
Isolation Method | Internal circuit: photocoupler isolated (isolation protection put to AC500V rms) Between input terminals: not isolated |
Output Specifications (Q0, Q1)
Output Points | 2 points |
---|---|
Output Type | Source output |
Common Design | 2 points/ 1common |
Maximum Load Current | 1A per common line |
Voltage drop (on voltage) | DC1V (max.) (voltage between COM and output terminals when output is on) |
Output Delay Time | 5μs (max.) 5μs (max.) |
Isolation Method | Between output terminal and internal circuit: photocoupler isolated (isolation protection up to AC500 V rms) Between output terminals: not isolated |
Output Specifications (Q2 to Q7)
Output Points | 6 points |
---|---|
Output Type | Relay output |
Common Design | COM1: 3, NO contacts COM2: 2, NO contacts COM3: 1, NO contacts |
Maximum Load Current | 2A per output, 8A per common line |
Output Delay Time | 10ms (max.) (Bounce time not included) 5ms (max.) (Bounce time not included) |
Isolation Method | Between output to internal circuit: AC1500Vrms, 1min Between output to terminals (COMs): AC750Vrms, 1min |